These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours.
60 Hz Prime Rating
These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these ratings. The alternator on this model is peak continuous rated (as defined in ISO 8528-3).
50 Hz Standby Rating
Standard reference conditions 25�C (77�F) Air Inlet Temp, 100m (328 ft) A.S.L. 30% relative humidity. Fuel consumption data at full load with diesel fuel with specific gravity of 0.85 and conforming to BS2869: 1998, Class A2.
Engine Specifications
Engine Model
Perkins® 1103D-33G3
Bore
105 mm (4.1 in)
Stroke
127 mm (5 in)
Governor Type
Mechanical
Displacement
3.3l (201.4 cu. in)
Compression Ratio
19.25:1
Benefits & Features
FG Wilson Diesel Engine
Perkins Engine
Alternator
Benefiting from a choice of leading alternators, the range incorporates the Marelli alternator as standard across three phase models.
DCP-10
The FG Wilson DCP range allows you to monitor and control your generator set with ease, providing important diagnostic information whilst ensuring your unit operates within safe parameters. FG Wilson DCP digital control panels, provide simple, intuitive menu navigation and control of your generator set operations. Key information is displayed via the LCD screen and LED’s using universally recognised symbols, eliminating the need for complex instructions or language settings.
Design Criteria
Prime Rating These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours. Standby Rating These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these ratings. The alternator on this model is peak continuous rated (as defined in ISO 8528-3). Standard Reference Conditions Note: Standard reference conditions 25°C (77°F) Air Inlet Temp, 100m (328 ft) A.S.L. 30% relative humidity. Fuel consumption data at full load with diesel fuel with specific gravity of 0.85 and conforming to BS2869: 1998, Class A2.
Single-Source Supplier
Fully prototype tested with certified torsional vibration analysis available
World Wide Product Support
FG Wilson manufactures product in the following locations: Northern Ireland • Brazil • China • India • USA With headquarters in Northern Ireland, FG Wilson operates through a Global Dealer Network.
Optional Equipment
Exhaust
Industrial, Residential, Critical Silencers
Alternator
Upgrade to Leroy Somer Alternator
Quadrature Droop Kit (AR6)
Anti-Condensation Heater and Panel Circuitry (AH1)
Control Panels
PowerWizard 1.1 Control Panel (PWT1.1)
PowerWizard 1.1+ Control Panel (PWT1.1+)
PowerWizard 2.1 Control Panel (PWT2.1)
Starting/Charging
Lead Acid battery (Dry)
General
Upgrade to Standard Set for “CE” Certification
EEC Declaration of Conformity
Narrow, Wide or Skid Base
Sound attenuated, steel or galvanised enclosure
Dual wall fuel tanks
Standard Equipment
Engine
Air Cleaner
Lube oil drain valve
Engine filled with lubrication oil
High Coolant Temperature Shutdown
Low Oil Pressure Shutdown
Cooling
Radiator & Cooling Fan
Coolant Drain Valve
Fan, Fan drive and battery charging Alternator drive fully guarded to meet EC Machinery Directive
Cooling System filled with Coolant mix
Exhaust
Exhaust flange outlet
Exhaust stub pipe and gasket
Fuel
8 Hr Fuel Tank
Fuel Fittings for Local and Remote Feed
Alternator
Marelli
SHUNT Excitation
IP23 Protection
Control Panel
DCP-10
Mounting
Base, Formed Steel with Single wall Fuel Tank
Certified Base Mounted Lifting Eyes, and Rear Drag Eyelets