PRO150-1

Minimum Rating
150 kVA / 120 kW

Maximum Rating
172 kVA / 137 kW

Emissions/Fuel Strategy
EU3a Emissions Compliant


SKU: 8d868c8e3980 Categories: ,

Full Specifications

Generator Set Specifications

Minimum Rating 150 kVA / 120 kW
Maximum Rating 172 kVA / 137 kW
Emissions/Fuel Strategy EU3a Emissions Compliant
50 Hz Prime 150 kVA / 120 kW
60 Hz Prime 172 kVA / 137 kW
Frequency 50 / 60 Hz Switchable
Speed 1500 or 1800 RPM
Voltage 127-480 Volts

Engine Specifications

Engine Model 1106A-70TAG2
Bore 105 mm (4.1 in)
Stroke 135 mm (5.3 in)
Governor Type A4:E2
Displacement 7L
Compression Ratio 18.2:1

Benefits & Features

FG Wilson Diesel Engine

Perkins Diesel Engine

 

Alternator

Benefiting from a choice of leading alternators, the range incorporates the Leroy Somer alternator as standard across three phase models.

 

PowerWizard 2.1+

The FG Wilson PowerWizard range of digital control panels, combine straightforward menu navigation with advanced metering and protection technology. They are used in automatic mains failure applications in conjunction with transfer panels. Our PowerWizard range allows you to monitor and control your generator set with ease, whilst ensuring your unit operates within safe parameters and provides important diagnostic information when needed.

 

Design Criteria

Prime Rating These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours. Standby Rating These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these ratings. The alternator on this model is peak continuous rated (as defined in ISO 8528-3). Standard Reference Conditions Note: Standard reference conditions 25°C (77°F) Air Inlet Temp, 100m (328 ft) A.S.L. 30% relative humidity. Fuel consumption data at full load with diesel fuel with specific gravity of 0.85 and conforming to BS2869: 1998, Class A2.

 

Single-Source Supplier

Fully prototype tested with certified torsional vibration analysis available

 

World Wide Product Support

FG Wilson manufactures product in the following locations: Northern Ireland • Brazil • China • India With headquarters in Northern Ireland, FG Wilson operates through a Global Dealer Network.

Optional Equipment

Exhaust

  • Industrial, Residential, Critical Silencers

Alternator

  • Quadrature Droop Kit
  • Anti-Condensation Heater and Panel Circuitry

Starting And Charging

  • 12V battery charger
  • UL/CSA listed 120 V, 20 Amp battery charger, shock mounted and enclosed in dust proof housing

General

  • CE socket box with integrated MCB and RCBO protection
  • Clipsal socket box with integrated MCB and RCBO protection
  • Anti-condensation heater 110 or 230 VAC
  • Coolant heater 110 or 230 VAC
  • Lube oil sump pump

Standard Equipment

Engine

  • Air Cleaner
  • Lube oil drain valve
  • Engine filled with lubrication oil
  • High Coolant Temperature Shutdown
  • Low Oil Pressure Shutdown

Cooling

  • Package mounted radiator
  • Radiator & Cooling Fan
  • Coolant Drain Valve
  • Fan, Fan drive and battery charging Alternator drive fully guarded to meet EC Machinery Directive
  • Cooling System filled with Coolant mix

Exhaust

  • Exhaust flange outlet
  • Exhaust stub pipe and gasket

Fuel

  • 590L double wall fuel tank, 24 hr runtime @ 75% prime rating, internal fuel fill
  • Fuel Fittings for Local and Remote Feed

Alternator

  • Leroy Somer
  • SHUNT Excitation
  • IP23 Protection

Control Panel

  • PowerWizard 2.1+

Mounting

  • Generator set soft mounted using captive vibration mounts
  • Heavy duty steel base frame contains integral double wall fuel tank
  • Provides 110% spill containment of all engine fluids
  • Forklift pockets and heavy duty drag bar with skid plates