PRO60-2
Minimum Rating
60 KVA / 47.2 KW
Maximum Rating
60 KVA / 48 KW
Frequency
EU3a Emissions Compliant
Full Specifications
Generator Set Specifications
Engine Specifications
Benefits & Features Optional Equipment Exhaust
Industrial, Residential, Critical Silencers
Alternator
Permanent Magnet Generator (PMG)
Anti-condensation heater 110 or 230 VAC
Starting/Charging
12V battery charger
UL/CSA listed 120 V, 20 Amp battery charger, shock mounted and enclosed in dust proof housing
General
CE socket box with integrated MCB and RCBO protection
Clipsal socket box with integrated MCB and RCBO protection
Coolant heater 110 or 230 VAC
CE labelling (also available for BSFC)
Standard Equipment Engine
Air Cleaner
Lube oil drain valve
Engine filled with lubrication oil
High Coolant Temperature Shutdown
Low Oil Pressure Shutdown
Cooling
Cooling package mounted radiator with high ambient capability
Pusher fan with guards
Coolant drain line with internal brass ball control valve piped to base-frame
Low coolant level shutdown.
50% coolant antifreeze with corrosion inhibitor
Exhaust
Integrated spark arresting silencer with flexible connectors, in separate compartment
Fuel
301L double wall fuel tank, 24 hr runtime @ 75% prime rating
Auxiliary connections for customer supplied fuel transfer with 3 way fuel transfer system, internally mounted within the bunded area.
Alternator
Leroy Somer
SHUNT Excitation
IP23 Protection
Control Panel
Mounting
Generator set soft mounted using captive vibration mounts
Heavy duty steel base frame contains integral double wall fuel tank
Provides 110% spill containment of all engine fluids
Forklift pockets and heavy duty drag bar with skid plates
This site uses and sets "cookies" on your computer to help make this website better. By continuing to use this site without changing your settings, you are agreeing to our use of cookies. Accept Read more